Example of Fault
    Fault Name   Ref:   Fault Information   Momentary  Confirmed
                                                           Message
 When RECR is up continuously for more than 2 seconds
 - in that condition if UCR/LR/U(R)S is up and HR/GR2 is   S1 Signal Flying
 9  Signal Flying Back to Danger  RDSO   M   C (120 Sec)
 down  and  signal  replacement  track(TPR)  is  up  and   back to Danger
 EGGNR down, then it is Signal Flying back to danger.

 The TIME difference between JSLR UP and NJPR UP is
                                                      S1 Timer setting
 10  Timer Setting More   RDSO  greater by more than 10% (more than 132 seconds for   M
                                                      More
 120 seconds timer) of the prescribed time.
                                                      101 WNR Button
 11  Button Stuck Up      Button relay is up for more than specified time 20 Sec      C
                                                      Relay Stuck Up
 In  between  two  sequential  TPRs  Down  to  Up  (To
 ensure it is train movement) if the status of NWKR or
 12  Point Loose Packing   RDSO  RWKR Changes more than 2 times and status of EWNR      C   59 Point Loose
                                                      Packing
 not  changed  (Point  emergency  operation  not  done)
 then it is Loose Packing.

 13  Signal Bobbing without      If HR/DR is up and HECR/DECR changes its status from
 Design Problem (i.e Signal
 Up to Dn to Up is in between 500 msec to 2 Sec and   S1 HECR Signal
 Control Relay not Dropped)
 HECR/DECR is not operated along with HR/DR then it is   M      Bobbing without
 Sig  Not  Applicable  Bobbing  without  design  problem.   Design Problem
 ECR is triggering sig Not Applicable.
 14  Signal Bobbing with Design
 If HR/DR is up, HECR/DECR changes its status from Up
 Problem (i.e Signal Control   to  Dn  to  Up  is  in  between  500  msec  to  2  Sec  and   S1 HECR Signal
 Relay Dropped)
 HECR/DECR is operated along with HR/DR then it is Sig   M      Bobbing with
 Not  Applicable  Bobbing  with  design  problem.ECR  is   Design Problem
 triggering sig Not Applicable.

 15  Signal not Lowered even      Same as Logic no.19      C
 Operation is Valid